Guardplc controller as a scanner – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 201

Publication 1753-UM001C-EN-P - March 2010
201
Introduction to EtherNet/IP Communication Chapter 18
GuardPLC Controller as a Scanner
The scanner data memory is divided into input and output buffers of
assemblies. The input area is used for signals received from the target
(consumed data). The output area is used for signals transmitted to
the target (produced signals). Each I/O assembly must have a
corresponding signal connection. Signal connections are configured
by using RSLogix Guard PLUS! software. The scanner data memory is
configured via a scanlist by using RSNetWorx for EtherNet/IP software.
To enable the GuardPLC controller to scan I/O, set up the controller
as a scanner. See
for information on using the GuardPLC
controller as a scanner.
FLEX I/O, POINT I/O,
ControlLogix or
CompactLogix Controllers
100
Outputs
101
Inputs
Input Assemblies
(IN_120)
Output Assemblies
(OUT_121)
ControlLogix Scanner
CompactLogix Scanner
Generic Device
PLC-5
SLC 5/05
PanelView Standard
(Via Explicit Messages)
Read/Write
Read
Produced Signals
Consumed Signals
Consumed Signals
Produced Signals
Scanner Assemblies
Adapter (Target)
Assemblies
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems