Appendix B System Signal Variables

Digital Input Module Variables for GuardPLC 1600 Controllers and
Distributed I/O

The GuardPLC 1600 controllers and distributed I/O support these
digital input parameters.

Module.Error.Code

Read

Error mask for the module

0x0000

I/O processing may be running with errors

0x0001

No I/O processing (CPU not in RUN)

0x0002

No I/O processing during start-up tests

0x0004

Manufacturing interface running

0x0010

No I/O processing due to incorrect configuration

0x0020

No I/O processing due to exceeded fault rate

0x0040/80

No I/O processing because configured module is not plugged in

I/O Data

Read/Write

Description

I/O Data

Read/Write

Description

DI.Error Code Supply
(1753-IB16XOB8 only)

Read

0x0001

Error in the total module DI supply.

DI[xx].Error Code Supply
(1753-IB16XOB8 only)

Read

Error mask of all digital inputs

0x01

Error in DI supply of the module.

0x02

Supply is switched off due to overcurrent.

0x04

Error in reading back the supply.

DI.Error Code

Read

Error mask for all digital inputs

0x0001

Error in digital input range

0x0002

FTZ test of test pattern failed

DI[xx].Error Code

(1)

Read

Error mask of all digital input channels

0x01

Error in digital input module

0x10

Short-circuit of the channel

0x80

Line interrupt between pulse output (DO) and pulse input (DI)

DI[xx].Value

(1)

Write

Input value of digital input channels

0

Input not set

1

Input set