Choose online or offline diagnostics, Filtering diagnostic data – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual
Page 141

Publication 1753-UM001C-EN-P - March 2010
141
Diagnostics Chapter 15
Choose Online or Offline Diagnostics
When you start the diagnostics window, Diag. Online is automatically
activated. This signals that you want all diagnostics data transferred
from the controller to the diagnostics buffer in RSLogix Guard PLUS!
software. As long as Diag. Online is active, new diagnostic data is
transferred to this buffer as it becomes available and if the filter you
selected applies.
Diag. Offline disconnects communication with the controller. This
ends the transmission of diagnostic data from the controller to the
diagnostics buffer in RSLogix Guard PLUS! software.
Filtering Diagnostic Data
Choose from these filters to determine what diagnostic data to display.
Filter
Description
Start At Oldest Entry
Displays all the data from the RSLogix Guard PLUS! software buffer starting with the
oldest entry.
The number of lines shown in the table depends on the Entries Per Diag. Enable Sorting
defaults to disabled so that the data appears in chronological order from oldest to newest.
Start At Newest Entry
Displays all the data from the RSLogix Guard PLUS! software buffer starting with the
newest entry.
The number of lines shown in the table depends on the Entries Per Diag. Enable Sorting
defaults to disabled so that the data appears in chronological order from oldest to newest.
Start At Date
Displays entries in chronological order starting at this date and time.
The number of lines shown in the table depends on the Entries Per Diag.
Enter the date as mm/dd/yy and the time as hh:mm.
Stop At Date
Displays entries in chronological order ending at this date and time.
The number of lines shown in the table depends on the Entries Per Diag.
Enter the date as mm/dd/yy and the time as hh:mm.
Entries Per Diag.
Determines the maximum number of entries to load into the buffer for the CPU and COM
diagnostics.
For example, if you enable short term and long term diagnostics for CPU and COM and you
set Entries Per Diag. = 10, the diagnostic window contains a maximum of 40 entries
(10 entries per diagnostic type).
RSLogix Guard PLUS! software can buffer as many as 5000 entries per type of diagnostic.
Sort
If Sort is disabled, the diagnostic window displays entries in the order they were saved in
the controller.
If Sort is enabled, the diagnostic window automatically displays entries according to date.
CPU Short Term Diagnostic
CPU Long Term Diagnostic
COM Short Term Diagnostic
COM Long Term Diagnostic
Enables or disables whether to display the diagnostic data for each type.
- 1755-HSC GuardPLC Controller Systems 1755-IF8 GuardPLC Controller Systems 1755-IB24XOB16 GuardPLC Controller Systems 1755-A6 GuardPLC Controller Systems 1755-L1 GuardPLC Controller Systems 1754-L28BBB GuardPLC Controller Systems 1753-IB20XOB8 GuardPLC Controller Systems 1753-OB16 GuardPLC Controller Systems 1753-IB16 GuardPLC Controller Systems 1753-L32BBBP-8A GuardPLC Controller Systems 1753-L32BBBM-8A GuardPLC Controller Systems 1753-L28BBBP GuardPLC Controller Systems 1753-L28BBBM GuardPLC Controller Systems