I/O Data

Read/Write

Description

Board.SRS

Read

System.Rack.Slot

Board.Type

Read

Module type

0x00E1

digital I/O module for GuardPLC 1200 controllers

0xFE01

digital I/O module for GuardPLC 2000 controllers

0xFFFF

missing module in GuardPLC 2000 chassis

Board.State

(1)

Read

Error mask for the module

0x000

I/O processing may be running with errors

0x001

No I/O processing (CPU not in RUN)

0x002

No I/O processing during start-up tests

0x004

Manufacturing interface running

0x010

No I/O processing due to faulty parameterization

0x020

No I/O processing due to exceeded fault rate

0x040

No I/O processing because configured module is not plugged in