1755-ib24xob16 module status indicators, Serial communication indicators, Power supply and module status – Rockwell Automation 1755-OF8 GuardPLC Controller Systems User Manual

Page 147

Advertising
background image

Publication 1753-UM001C-EN-P - March 2010

147

Diagnostics Chapter 15

Serial Communication Indicators

1755-IB24XOB16 Module
Status Indicators

The 1755-IB24XOB16 digital combination input and output module
(AB-DIO) has status indicators for:

power supply.

module status.

I/O status.

Power Supply and Module Status

Indicator

Status

Description

FB1

On

Field bus no. 1 is active

FB2

On

Field bus no. 2 is active
(serial interface module)

IMPORTANT

Only the bottom serial port on the GuardPLC 2000 controller is
active, as indicated by the FB2 status indicator.

FB1

FB2

RUN ERR

1755-

IB24XOB16

RUN ERR

1
2
3
4
5
6
7
8
9

LS+

I1

I2

I3

I4

I5

I6

I7

I8

Indicator

Status

Description

RUN

On (green)

The module has the correct operating voltage (24V DC).

Off

The module has no power.

ERR

On (red)

If the system is in Stop mode, one or more of the inputs or
outputs is faulty, or the module is faulty.

Use the RSLogix Guard PLUS! software to verify the location
of the fault. If the module is faulty, replace the module
immediately, or the safety-related operation of the
GuardPLC 2000 controller is not maintained.

Off

The module is operational.