5 Operation

5.3.5 Zero Clamp Function

5-28

(2) Changing Input Signal Allocations (Pn50A.0 = 1)

Use the /ZCLAMP signal when switching to zero clamp function.

Note: Use parameter Pn50D.0 to allocate the /ZCLAMP signal for use. For details, refer to 3.3.1 Input Signal Allocations.

To use the zero clamp function, set Pn000.1 to 0, 3, 4, 5, 6, 7, 9 or A.

Note: If Pn000.1 is set to 5, 6, 7, or 9, the zero clamp function will become invalid when the control is changed to any

methods other than speed control and internal set speed control.

For speed control, the zero clamp function locks the servomotor when the speed reference drops below the set
speed in the zero clamp level by setting Pn50D.0 to 7 (zero clamp function is always valid). The input signals

(/ZCLAMP, /P-CON) are not necessary.

(3) Related Parameter

Set the motor speed at which to enter zero clamp operation.

Note: Even if a value that exceeds the maximum speed of the servomotor is set, the actual speed will be limited to the max-

imum speed of the servomotor.

Type

Connector

Pin Number

Setting

Meaning

Input

/ZCLAMP Must be allocated

ON
(closed)

The zero clamp function will be turned ON if the input volt-
age of the speed reference (V-REF) drops below the set speed

in the zero clamp level (Pn501).

OFF
(open)

Turns OFF the zero clamp function.

Parameter

Control Method

Input Signal

Used

When Enabled Classification

Pn000

n.

0

Speed control

/ZCLAMP

After restart

Setup

n.

3

Internal set speed control

/ZCLAMP,
SPD-A,

SPD-B,
SPD-D,
C-SEL

n.

4

Internal set speed control <=> Speed
control

/ZCLAMP,
SPD-A,
SPD-B,
SPD-D,
C-SEL

n.

5

Internal set speed control <=> Posi-
tion control

/ZCLAMP,
SPD-A,
SPD-B,
SPD-D,
C-SEL

n.

6

Internal set speed control <=> Torque
control

/ZCLAMP,
SPD-A,
SPD-B,
SPD-D,
C-SEL

n.

7

Position control <=> Speed control

/ZCLAMP,
C-SEL

n.

9

Torque control <=> Speed control

/ZCLAMP,
C-SEL

n.

A

Speed control <=> Speed control with
zero clamp function

/ZCLAMP,
C-SEL

Pn501

Zero Clamp Level

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 10000

1 min

-1

10

Immediately

Setup

Speed