5.8 Limiting Torque

5-61

5

Ope

rat

ion

(3) Changes in Output Torque during External Torque Limiting

The following diagrams show the change in output torque when the internal torque limit is set to 800%.

In this example, the servomotor rotation direction is Pn000.0 = 0 (Sets CCW as forward direction).

5.8.3 Torque Limiting Using an Analog Voltage Reference

For torque limiting by analog voltage reference, the torque is limited by using the analog voltage at the T-REF

terminals for CN1-9 and CN1-10.

From the torque limit value by analog reference and torque limit value by Pn402 and Pn403, whichever is
smaller will be applied.

This function can be used only during speed or position control, not during torque control.

The following chart shows when the torque limiting using an analog voltage reference is performed in the

speed control.

There is no polarity in the input voltage of the analog voltage reference for torque limiting. The absolute val-

ues of both + and - voltages are input, and a torque limit value corresponding to that absolute value is applied
in the forward and reverse direction.

/P-CL

OFF

ON

/N-CL

OFF

ON

Pn402

Pn403

0

Torque

Speed

Pn403

0

Pn404

Pn402

Torque

Speed

0

Pn403

Pn405

Pn402

Torque

Speed

0

Pn403

Pn405

Pn404

Pn402

Torque

Speed

Parameter

Meaning

When Enabled Classification

Pn002

n.

1

Uses the T-REF terminal as an external torque limit
input.

After restart

Setup

Pn300

+

+

+

-

Pn400

T-REF

V-REF

T-REF filter time constant

Pn101

Pn415

Pn100

Torque reference input gain

Pn402

Speed
loop
gain

Speed feedback

Torque limit
value

Speed
reference

Torque
reference

Forward
torque limit

Pn403
Reverse torque limit

SERVOPACK

Speed
reference input
gain

Speed loop
integral time
constant

(See 5.5.1.)

(See 5.3.1.)

(See 5.8.1.)

(See 5.8.1.)

(See 6.9.2.)