6.9 Compatible Adjustment Function

6-69

6

Adjustm

e

nts

6.9.4 Proportional Control

The /P-CON signal can be sent from the host control to select proportional control.

The speed control section uses a PI control if the reference stays zero in the speed control. This integral effect
may cause the servomotor to move. Switch the PI control to a proportional control to prevent this from occur-

ring.

If the speed control is set with a zero clamp function, however, a position loop will be formed so there is no

need to use this function. The speed control is set to proportional control if the /P-CON signal is ON.

Proportional control operation is set using parameter Pn000.1 and input signal /P-CON.

(1) /P-CON Input Signal

Input signal /P-CON is used to switch between PI control and P control.

Example: Factory-set Input Signal Allocations

Note: This is an example when the input signal allocations are at the default factory settings.

(2) Control Method and Proportional Control Input Signal

Proportional control operation is enabled when the control method is set to speed or position control.

Note: Refer to 5.7 Combination of Control Methods for how to switch control methods.

Type

Signal

Name

Connector

Pin Number

Setting

Meaning

Input

/P-CON

CN1-41
[Factory setting]

OFF (High level)

Switches to PI control (proportional-integral

control).

ON (Low level)

Switches to P control (proportional control).

SERVOPACK

/P-CON

P/PI Switching

41

CN1

Analog

Parameter

Contents

Switching to the Proportional

Control

Pn000

n.

0 [Fac-

tory setting]

Speed control

Can be switched with the factory
setting (CN1-41=/P-CON).
/P-CON signal can be allocated to
other terminals as required.

n.

1

Position control

n.

2

Torque control

Cannot switch to proportional
control.

n.

3

Internal set speed control

Allocation of /P-CON to one of
terminals CN1-40 to 46 are
needed.

n.

4

Internal set speed control

Speed control

n.

5

Internal set speed control

Position control

n.

6

Internal set speed control

Torque control

n.

7

Position control

Speed control

n.

8

Position control

Torque control

n.

9

Torque control

Speed control

n.

A

Speed control

Speed control with zero clamp

function

n.

B

Position control

Position control with reference

pulse inhibit function