7.8 Offset Adjustment of Analog Monitor Output (Fn00C)

This function is used to manually adjust the offsets for the analog monitor outputs (torque reference monitor

output and motor speed monitor output). The offset values are factory-set before shipping. Therefore, the user

need not usually use this function.

(1) Adjustment Example

An example of offset adjustment to the motor speed monitor is shown below.

Note:

• The adjustment value will not be initialized when parameter settings are initialized using Fn005.
• Make offset adjustment with a measuring instrument connected, so that the analog monitor output is zero. An

example of settings for a zero analog monitor output is shown below.

• While the servomotor is not turned ON, set the monitor signal to the torque reference.
• In speed control, set the monitor signal to the position error.

(2) Preparation

The following condition must be met to adjust the offsets of the analog monitor output.

• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).

(3) Operating Procedure

Use the following procedure to perform the offset adjustment of analog monitor output.

Item

Specifications

Offset Adjustment Range

-2.4 V to + 2.4 V

Adjustment Unit

18.9 mV/LSB

Analog monitor output
voltage

Motor speed

Offset
adjustment

Step

Display after Opera-

tion

Keys

Operation

1

Press the MODE/SET Key to select the utility function.

2

Press the UP or DOWN Key to select Fn00C.

3

Press the DATA/SHIFT Key for approximately one second.
The display shown on the left appears.

MODE/SET

DATA/

MODE/SET

DATA/

MODE/SET

DATA/