5 Operation

5.5.3 Torque Reference Filter

5-50

5.5.3 Torque Reference Filter

This smooths the torque reference by applying a first order lag filter to the torque reference (T-REF) input.

Note: A setting value that is too large, however, will slow down response.

Check the response characteristics when setting this parameter.

5.5.4 Speed Limit in Torque Control

This function limits the speed of the servomotor to protect the machine.

A servomotor in torque control is controlled to output the specified torque, but the motor speed is not con-

trolled. Therefore, if an excessive reference torque is set for the load torque on the machinery side, the speed
of the servomotor may increase greatly. If that may occur, use this function to limit the speed.

Note: The actual limit value of motor speed depends on the load conditions of the servomotor.

Refer to the following parameters for speed limit.

(1) Signals Output during Servomotor Speed Limit

The following signal is output when the motor speed reaches the limit speed.

Note: Use parameter Pn50F.1 to allocate the /VLT signal for use. For details, refer to 3.3.2 Output Signal Allocations.

(2) Speed Limit Setting

Select the speed limit mode with Pn002.1.

Pn415

T-REF Filter Time Constant

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 65535

0.01 ms

0

Immediately

Setup

Speed

Position

Torque

With No Speed Limit

With Speed Limit

Motor speed

Time

Maximum speed

Danger of damage due to
critical speed.

Motor speed

Limiting speed

Safe operation with
speed limit.

Time

Type

Signal

Name

Connector

Pin Number

Setting

Meaning

Output

/VLT

Must be allocated

ON (closed)

Servomotor speed limit being applied.

OFF (open)

Servomotor speed limit not being applied.

Parameter

Meaning

When

Enabled

Classification

Pn002

n.

0

[Factory setting]

Uses the value set in Pn407 as the speed limit (internal
speed limit function).

After restart

Setup

n.

1

Uses V-REF (CN1-5, 6) as an external speed limit
input. Applies a speed limit using the input voltage of
V-REF and the setting in Pn300 (external speed limit
function).