3.7 Noise Control and Measures for Harmonic Suppression

3-47

3

Wi

ring an

d Conn

ecti

on

Connect the noise filter ground wire directly to the ground plate.

Do not connect the noise filter ground wire to other ground wires.

If a noise filter is located inside a control panel, first connect the noise filter ground wire and the

ground wires from other devices inside the control panel to the ground plate for the control panel,

then ground the plates.

3.7.3 Connecting a Reactor for Harmonic Suppression

The SERVOPACK has reactor connection terminals for power supply harmonic suppression that can be used

as required. Refer to

Σ

-V Series Product Catalog (No.: KAEP S800000 42) for precautions on selecting an AC

or DC reactor and its specifications.

Connect a reactor as shown in the following diagram.

Note 1. Connection terminals for DC reactor

1 and 2 are short-circuited at shipment. Remove the lead wire for

short-circuit, and connect a DC reactor.

2. Reactors are not included. (Sold separately.)
3. DC reactors cannot be connected to SERVOPACKs with a single-phase 100-V power input.

Shielded
ground wire

Noise
Filter

Noise
Filter

SERVOPACK SERVOPACK

SERVOPACK SERVOPACK

Ground plate

Ground plate

Incorrect

Correct

Noise
Filter

Control Panel

Ground

SERVOPACK

SERVOPACK

Ground plate

SERVOPACK with 100-VAC Power Input

SERVOPACK with 200/400-VAC Power Input

L1

L2

SERVOPACK

AC reactor

Power
supply

1

2





SERVOPACK