5.4.1 Basic Settings for Position Control

5-34

(3) Connection Example

The following diagram shows a connection example. Use an SN75ALS174 or MC3487 manufactured by

Texas Instruments Inc., or equivalent for the line driver.

Line Driver Output

represents twisted-pair wires.

Open-collector Output

Set limit resistor R so the input current, i, falls between 7 mA to 15 mA.

represents twisted-pair wires.

Line driver

SERVOPACK

Host controller

CN1

7

8

14

15

12

11

PULS

SIGN

CLR

/PULS

SIGN

/SIGN

CLR

/CLR

PULS

CW

Phase A

CCW

Phase B

150

Ω

4.7 k

Ω

Photocoupler

150

Ω

4.7 k

Ω

Photocoupler

150

Ω

4.7 k

Ω

Photocoupler

FG

FG

45

• Use a shielded cable for I/O signals and ground both ends of the shield.
• Connect the shield of the cable on the SERVOPACK side to the connector shell so

that the shield will be connected to the frame ground (FG) through the connector.

CN1

7

8

14

15

12

11

/PULS

SIGN

/SIGN

CLR

/CLR

PULS

150

Ω

4.7 k

Ω

4.7 k

Ω

4.7 k

Ω

150

Ω

150

Ω

FG FG

Vcc

Vcc

Vcc

Tr

Tr

Tr

R

R

i

i

i

R

SERVOPACK

Host controller

Example

When Vcc is +12 V: R = 1 kΩ

When Vcc is +24 V: R = 2.2 kΩ

When Vcc is +5 V: R = 180 Ω

Note: In case of open-collector outputs,
the signal logic is as follows.

When Tr is ON

High level input or
equivalent
Low level input or
equivalent

When Tr is OFF

Photocoupler

Photocoupler

Photocoupler

Analog