64 (1) input signals, 2) related parameters – Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors - Analog Voltage and Pulse Train Reference User Manual

Page 178

Advertising
background image

5 Operation

5.8.4 Torque Limiting Using an External Torque Limit and Analog Voltage Reference

5-64

(1) Input Signals

Use the following input signals to limit a torque by external torque limit and analog voltage reference.

Refer to 5.5.1 Basic Settings for Torque Control.

(2) Related Parameters

Set the following parameters for torque limit by external torque limit and analog voltage reference.

The setting unit is a percentage of the rated torque.

Type

Signal Name

Connector

Pin Number

Name

Input

T-REF

CN1-9

Torque reference input

SG

CN1-10

Signal ground for torque reference input

Type

Signal

Name

Connector

Pin Number

Setting

Meaning

Limit Value

Input /P-CL

CN1-45
[Factory setting]

ON

Forward external torque limit ON

The smallest value of these set-

tings: the analog voltage refer-
ence limit, Pn402, or Pn404

OFF

Forward external torque limit
OFF

Pn402

Input /N-CL

CN1-46
[Factory setting]

ON

Reverse external torque limit ON

The smallest value of these set-

tings: the analog voltage refer-
ence limit, Pn403, or Pn405

OFF

Reverse external torque limit
OFF

Pn403

Pn400

Torque Reference Input Gain

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

Setup

10 to 100

0.1 V

30 (Rated torque at

3.0 V)

Immediately

Pn402

Forward Torque Limit

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

Setup

0 to 800

1%

800

Immediately

Pn403

Reverse Torque Limit

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

Setup

0 to 800

1%

800

Immediately

Pn404

Forward External Torque Limit

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

Setup

0 to 800

1%

100

Immediately

Pn405

Reverse External Torque Limit

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

Setup

0 to 800

1%

100

Immediately

Pn415

T-REF Filter Time Constant

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 65535

0.01 ms

0

Immediately

Setup

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque

Speed

Position

Torque