5.4 Position Control

5-37

5

Ope

rat

ion

5.4.2 Clear Signal Setting

Clear input signal sets SERVOPACK error counter to zero.

(1) Connecting the Clear Signal

(2) Clear Input Signal Form

Set the clear input signal form using Pn200.1.

The following items will be changed in the SERVOPACK after the error counter has been reset to zero.

• The SERVOPACK error counter is set to 0.
• The position loop operation is disabled.

Note: Holding the clear status may cause the servolock to stop functioning and the servomotor to rotate slowly due to drift

in the speed loop.

Pulse Width of Clear Signal

When parameter Pn200.1 is set to 0 or 2, the width of the clear signal must be at least 250

μs to reset the error

counter.

When parameter Pn200.1 is set to 1 or 3, the width of the clear signal must be at least 20

μs to reset the error

counter.

(3) Clear Operation

This parameter determines when the position error should be set to zero according to the condition of the SER-

VOPACK. Any of three clearing modes can be selected with Pn200.2.

Type

Signal Name

Connector Pin Number

Name

Input

CLR

CN1-15

Clear input

/CLR

CN1-14

Parameter

Description

Clear Timing

When

Enabled

Classification

Pn200

n.

0

[Factory setting]

Clears at ON.
Position errors do not

accumulate while the sig-
nal is ON.

After restart

Setup

n.

1

Clears at the rising edge.

n.

2

Clears at OFF.
Position errors do not
accumulate while the sig-
nal is OFF.

n.

3

Clears at the falling edge.

Clears at
ON.

CLR
(CN1-15)

ON

Clears here just once.

CLR

(CN1-15)

OFF.

CLR
(CN1-15)

Clears at

OFF

Clears here just once.

CLR

(CN1-15)

Parameter

Description

When

Enabled

Classification

Pn200

n. 0

[Factory setting]

Sets the position error to zero during a baseblock when
an alarm occurs or when the servo ON signal (/S-ON)
turns OFF.

After restart

Setup

n. 1

Does not set the error counter to zero. Clears the posi-
tion error only with the CLR signal.

n. 2

Sets the position error to zero when an alarm occurs.