7-12

7.6 Initializing Parameter Settings (Fn005)

This function is used when returning to the factory settings after changing parameter settings.

Note: Any value adjusted with Fn009, Fn00A, Fn00B, Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.

(1) Preparation

The following conditions must be met to initialize the parameter values.

• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servo ON signal (/S-ON) must be OFF.

(2) Operating Procedure

Use the following procedure.

• Be sure to initialize the parameter settings while the servo ON (/S-ON) signal is OFF

.

• After initialization, turn OFF the power supply and then turn ON again to validate the

settings.

Step

Display after Opera-

tion

Keys

Operation

1

Press the MODE/SET Key to select the utility function.

2

Press the UP or DOWN Key to select Fn005.

3

Press the DATA/SHIFT Key for approximately one second.
The display shown on the left appears.

4

Press the MODE/SET Key. Then, the parameters will be
initialized.
When the initialization has been completed, "donE" flashes
on the display and returns to the screen as shown on the left.

5

To enable the change in the setting, turn the power OFF and ON again.

MODE/SET

DATA/

MODE/SET

DATA/

MODE/SET

DATA/

MODE/SET

DATA/