3 application example of safety functions, 1) connection example, 2) failure detection method – Yaskawa Sigma-5 User Manual: Design and Maintenance - Rotary Motors - Analog Voltage and Pulse Train Reference User Manual

Page 202

Advertising
background image

5 Operation

5.11.3 Application Example of Safety Functions

5-88

5.11.3 Application Example of Safety Functions

An example of using safety functions is shown below.

(1) Connection Example

In the following example, a safety unit is used and the HWBB function operates when the guard opens.

When a guard opens, both of signals, the /HWBB1 and the /HWBB2, turn OFF, and the EDM1 signal turns

ON. Since the feedback is ON when the guard closes, the safety unit is reset, and the /HWBB1 and the /

HWBB2 signals turn ON, and the operation becomes possible.

Note: The EDM1 signal is used as a sourcing output. Connect the EDM1 so that the current flows from EMD1+ to EMD1-.

(2) Failure Detection Method

In case of a failure such as the /HWBB1 or the /HWBB2 signal remains ON, the safety unit is not reset when
the guard closes because the EDM1 signal keeps OFF. Therefore starting is impossible, then the failure is

detected.

In this case, an error in the external device, disconnection or short-circuiting of the external wiring, or a failure

in the SERVOPACK must be considered. Find the cause and correct the problem.

/HWBB1+

4

3

6

5

8

7

A1

A2

T11 T12 T21

T31 T32 T33

S24 S14

T22

/HWBB1-

/HWBB2+

/HWBB2-

EDM1+

EDM1-

0 V

CN8

SERVOPACK

Output

24-V power

supply

Guard

Safety unit G9SX-BC202

manufactured by OMRON Corp.

Fuse

Close

Limit switch

Power
supply

input

Input

Reset/feedback
input

Open

Advertising