5. Commissioning

5−23

Festo GDCP−SFC−LACI−IO−EN en 0812NH

Device control

When the SFC−LACI is switched on, the controller interface is
activated as standard [HMI= off ].

Caution
Unexpected movements of the drive due to incorrect
parametrising

·

Make sure that there is no active ENABLE signal on the
controller interface when switching on the SFC−LACI.

·

Parameterise the entire system completely before actiĆ
vating the controller with ENABLE (controller interface),
Enable" (FCT), or [HMI = on] (control panel).

In order that the FCT can control the connected SFC−LACI,
the SFC−LACI’s controller interface must be deactivated and
Controller enable" for the FCT must be set (FCT/HMI = On).
The actual status of the control bit ENABLE then has no effect.

·

To do this, tick the FCT" box in the window Project outĆ
put", tab Operate" under Device control".
The controller interface of the SFC−LACI will then be
deactivated and Control Enable will be set for the FCT.