B. Supplementary information
B−34
Festo GDCP−SFC−LACI−IO−EN en 0812NH
Position window time
CI
20E6h
01h...22h
Array
uint16
rw
Description
Damping time in milliseconds [ms].
If the actual position has been in the target position window for this amount of
time, the Motion complete" bit is set in the status word. Also referred to as
Adjustment time". Value range: 1 ... 60000 ms. Default: 10 ms.
Record 0
01h
Do not use (Homing)
Record ...
(positioning
...
(positioning
record ...) Damping time for position records 1...30
Record 31
20h
Damping time for position record 31
Jog mode
21h
Damping time with jog mode
Direct mode
22h
Damping time with direct mode
Note: The object 20E0h/07h is provided for access via CI.
6068h contains the damping time of the currently active record.