5. Commissioning
5−30
Festo GDCP−SFC−LACI−IO−EN en 0812NH
START: I8
Start positioning record
Note
When using a brake/clamping unit:
·
Observe the special features in conjunction with the
various delay times (see the example for the automatic
brake in section 5.5.6).
The execution of a positioning record is started by a rising
edge at the START input under the following preconditions:
ć
Logic 1 is active at READY.
ć
Logic 1 is at MC.
ć
Logic 1 is active at STOP.
ć
The desired positioning record is active at I1...I5.
Input
Status
START (input)
E8
0
> 1
Start of the positioning record.
The positioning record can be stopped (abort) with a falling
edge at the STOP input. If started again, the positioning reĆ
cord will be continued as from the current position.