5. Commissioning

5−34

Festo GDCP−SFC−LACI−IO−EN en 0812NH

Start−up characteristics
performance

In order to guarantee that the system starts correctly, all
input signals must be stable when the power supply is
switched on (at least 1 s ć depending on the amount of
stored EEPROM data). Only then are the input signals
queried.

*) If there are no errors (ERROR signal = 1) and enabling is
activated for the first time (ENABLE signal = 1), the drive
searches for its commutation point. It will vibrate for a few
seconds and move minimally. The SFC−LACI then reports
readiness to operate (READY signal

> 1).

Homing (input word I1 ... I5 = 0, positive edge at START
input) can then be started.
Other positioning records (I1 ... I5

š 0) cannot be started

(−> error PLEASE ENFORCE HOMING RUN!").

Start the homing run

When the START signal is set (

> 1), confirmation follows via

the ACK signal (

> 0). The MC signal (Motion Complete) is

reset (

> 0); the drive carries out the homing run.

When the START signal is reset (

> 0), confirmation follows

via the ACK signal (

> 1).

Once the homing run is complete, the MC signal is set again
(

> 1).

After that, any number of positioning procedures can be
executed; see Fig. 5/3.

Stopping the homing run

An ongoing homing run, like any positioning record, can be
stopped with a negative edge at the STOP input (

> 0), see

Fig. 5/2. The drive stops the motion with parameterisable
brake ramp. The MC signal (Motion Complete) is set (

> 1),

the READY signal is reset (

> 0).

Fault in the homing run

If an error occurs during the homing run, the drive is
stopped immediately; the MC signal, the READY signal and
the ERROR signal are reset (

> 0). The SFC−LACI reports an

error.