Festo Контроллеры двигателя SFC-LAC User Manual

Page 222

Advertising
background image

B. Supplementary information

B−60

Festo GDCP−SFC−LACI−IO−EN en 0812NH

Target torque/force

CI

6071h

00h

Var

int16

rw

Description

Nominal value for force control. Specified in permil of rated value (6076h).

Max. torque/force

CI

6072h

00h

Var

uint16

rw

Description

The highest permitted torque of the motor in permil of the rated value (6076h).
Values: 0...1000.

Max. current

CI

6073h

00h

Var

uint16

rw

Description

Maximum motor current in permil of rated current (6075h).
Note: The current limitation also limits the max. possible speed (or force).
Higher nominal speeds may not therefore be reached, or the drive stops.
During homing: At greatly reduced values combined with high travelling
resistance, there is a danger that the drive will come to a standstill and the
SFC−LACI will wrongly recognize a stop.

Motor rated current

CI

6075h

00h

Var

uint32

rw

Description

Nominal current of the motor in [mA]. The value is fixed.

Motor rated torque/force

CI

6076h

00h

Var

uint32

rw

Description

Nominal force of the linear motor in [mN]. The value is fixed.

Advertising