5. Commissioning

5−28

Festo GDCP−SFC−LACI−IO−EN en 0812NH

STOP: I6

Reset STOP signal or error (see Tab. 3/8)

Input

Status

STOP (input)

I6

1

> 0

With MC = logic 0:
Ĉ The drive stops with a parameterised

ramp (by default with Quick stop
deceleration", see section 1.3).

With ERROR = logic 0:
Ĉ Error is reset

0

> 1

After error acknowledgement or axis stop:
Ĉ Create readiness to operate READY

> 1

(only if ENABLE = 1)

A falling edge at the STOP input interrupts the positioning
record under the following preconditions:

ć

Logic 0 is at MC.

ć

Logic 1 is active at ERROR.

MC (Motion Complete) provides logic 0 until a positioning
record is interrupted with STOP (or the target has been
reached). The positioning record can be started again
with a rising edge at the START input (if STOP = 1).

An active error will be reset by a falling edge at the STOP
input under the following preconditions:

ć

Logic 0 is active at ERROR.

ć

Logic 0 is active at MC.

Readiness to operate is restored by a rising edge at the STOP
input under the following preconditions:

ć

Logic 1 is active at ENABLE.

ć

Logic 1 is active at ERROR.