Limitation of the speed set-value

Main and additional set-values are lined via the arithmetic block 1 and then limited
via a limitation element with adjustable limits (C286, C287). This function can be
used if certain negative or positive values must not be exceeded during operation.

JOG 1
JOG 2
JOG x

FDE

0

1

`

21

22

QSP

C134

QSP

C012 T
C013 T

ir
if

C190

0

1

C105

QSP

n

n

max

C046

C011

C145/C146

C049

C145/C146

C042

max

/

-

·

+

C46

100% - C49

C286 C287

n

100 %

FDE

FDE

FDE

C182

max

C050

Configuration C005 = -10- ... -53-

C041
CW/CCW

CW

CCW

Enable

RFG stop

RFG zero

set 1

in % of n

Z

off

set

n

at n-controller

in % of n

n-controller

set

SPI

C220, C221

set 2

4900Str031

FIG 7-4

Signal-flow chart for speed set-value selection with limitation element

Code

Name

Possible settings

Lenze

Selection

Info

C286*

¤ Upper limit

of the
speed
setpoint

180%

-100.0 %

{0.1 %}

+ 100.0 %

-180 %

{1 %}

+ 180 %

Upper limit of the speed setpoint for C050
C286 must be higher than C287!

C287*

¤ Lower limit

of the
speed
set-value

-180%

-100.0 %

{0.1 %}

+ 100.0 %

-180 %

{1 %}

+ 180 %

Upper limit of the speed setpoint for C050
C287 must be smaller than C286!