7-123

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C029

¤ Automatic

adjustment for
C025

C025 = -10-, -11-:
Adjustment of the digital frequency inputs X5, X9
-100.0%

{0.1%}

100.0%

Automatic adjustment only possible, if X5
or X9 are not selected as acutal speed
inputs:
1.Display of actual output value.
2.Enter required output value.
3.C027 displays the calculated gain

factor.

C025 = -12-
Adjustment of the resolver
-100.0%

{0.1%}

100.0%

Automatic adjustment is only possible, if
the resolver is not used as a speed
feedback system:
1.Display of actual output value.
2.Enter required output value.
3.C027 displays the calculated gain

factor.

C030

¤ Constant for the

digital frequency
output

1

-0-

8192 increments / revolution

-1-

4096 increments / revolution

-2-

2048 increments / revolution

-3-

1024 increments / revolution

-4-

512 increments / revolution

-5-

256 increments / revolution

Number of increments per revolution for
the digital frequency output

C032*

Ratio numerator 0.1000 -3.2767 {0.0001}

3.2767

Ratio numerator for configurations with
digital frequency
If an analog signal source is assigned
(C145/146), only the parameter will be
displayed.

C033*

Ratio
denominator

0.1000 0.0001

{0.0001}

3.2767

Ratio denominator for configurations with
digital frequency

C034*

¤ Master current

0

-0-

i

master

= -20 mA ... + 20 mA

-1-

I i

master

|= 4 mA ... 20mA

For master current input, the switch S3/1
must be set to ON.
C034 = -1-:
If i

master

< 2mA, the monitoring message

Sd5 will be displayed.

C038

¤ Input selection:

JOG setpoint

1

-1-

Selection JOG1

-2-

Selection JOG2

...
-15-

Selection JOG15

Select JOG setpoint to be set under C039.

C039

JOG speed for
C038

-100.0 % n

max

{0.1 %}

+ 100.0 % n

max

100.0%

JOG1

75.0%

JOG2

50.0%

JOG3

25.0%

JOG4

0.0%

JOG5

..

...

0.0%

JOG15

Enable JOG setpoints via the digital inputs
or via C045.

C040

Controller
enable

-0-

Controller inhibited

-1-

Controller enabled

Input only via LECOM1 or LECOM2. C183
indicates the source which has inhibited
the controller.

C041

¤ CW/CCW

direction of
rotation

-0-

Main setpoint not inverted

-1-

Main setpoint inverted

Input only with control via keypad or
interface.
Display only with terminal control.

C042

¤ Quick stop

-0-

No quick stop
(corresponds to X2/21 or X2/22 = HIGH)

-1-

Quick stop active
(corresponds to X2/21 and X2/22 = LOW)
Drives decelerates to standstill following the
quick-stop ramp C105.

Input only with control via keypad or
interface.
Display only with terminal control.

Show/Hide Bookmarks