2 dc tacho feedback, Dc tacho feedback, Configuration – Lenze EDS4900U-REG User Manual

Page 102

Advertising
background image

Configuration

7-11

48XX/49XXSHB0399

7.1.2.2

DC voltage tacho feedback

The actual speed value is fed back via X1/3 and X1/4. The tacho signal is
conditioned with a differential amplifier.

Stop!

Observe for tacho voltage adjustment, that also in field-weakening operation the
max. limit for the tacho input of 180 V must not be exceeded.

Possible configurations under C005:

-11-

Speed control with tacho feedback
(Default setting)

-41-

Torque control with speed limitation

For speed control with tacho feedback the analog actual value encoder must be
adjusted.

Adjustment of the tacho signal:

The analog inputs can be adjusted in respect of an offset or a gain fault. It is thus
possible to correct faults occuring in the controller or during transmission. The
value is adjusted to n

max

(C011).

n

set

adjustment (main set-value)

1. Inhibit controller via terminal X2/28.

2. Select max. set-value via X1/8.

3. Set C025 (”encoder selection”) to -4-.

4. Assign 100 % to the max. set-value under C029 (”automatic

adjustment”) (with

s or t 

(Adjustment of level tolerances in the set-value channel).

5. Acknowledge the adjustment with SH + PRG.

6. Set the speed set-value to approx. 50%.

n

act

adjustment

Stop!

The addition of the mains set-value and the additional set-value is limited to 180%
of n

max

! I.e. an addition of the additional set-value results in a motor speed of 1.8

¼ n

max

.

Observe max. motor speed and rated motor voltage!