Technical data – Lenze EDS4900U-REG User Manual

Page 33

Advertising
background image

Technical Data

3-5

48XX/49XXSHB0399

( Controllers 4808 to 4813 (2Q controllers)

Type

4808

4809

4811

4812

4813

Order No.

EVD 4808-E

EVD 4809-E

EVD 4811-E

EVD 4812-E

EVD 4813

Output power

1)

P

el

[kW]

152

230

322

460

552

Mains voltage

V

mains

3

ô 340...460 V~ á0%, 50...60Hz

Armature voltage

V

A

460 V if V

mains

= 400 V (1.15

¼ V

mains

)

Rated armature current
(continuous operation)

I

Arated

[A]

330

500

700

1000

1200

Maximum current
(short-time operation)

I

Amax

[A]

400

600

840

1200

1350

Field voltage

2)

V

F

V

Fmax

= 0.875

¼ V

L1-L3

Max. field current,
controlled

I

F

[A]

15

30

Power loss

3)

P

loss

[W]

830

1220

2100

2850

3400

Ambient temperature in
operation

T

amb

[

•C]

0...+ 35

4)

Weight approx.

[kg]

28

28

60

60

60

1)

referred to a mains voltage of 3

¼ 400V~

2)

The field is controlled as a current source, i.e. the field voltage depends on the field resistance.

3)

at rated armature current

4)

T

amb

$35°C: no power derating

,

35°C

T

amb

$45°C: power derating 1%/K