Troubleshooting and fault elimination – Lenze EDS4900U-REG User Manual

Page 250

Advertising
background image

Troubleshooting and fault elimination

8-5

48XX/49XXSHB0399

Display

Remedy

Cause

OUE

Mains overvoltage

Mains voltage > 460V or 550V (500V variant) Reduce mains voltage with a preconnected

transformer or
use a controller with a higher mains
connection voltage.

P03

Following error

Angle difference between set and actual
position is larger than the following error limit
set under C255
Drive cannot follow the digital frequency (I

max

limit)

Extend following limit with C255
Switch-off monitoring if required (C119/C120)
Enable drive (Ctrl. enable)
Check drive dimensioning

P13

Angle overflow

Angle controller limit reached
Drive cannot follow the digital frequency (I

max

limit)

Enable drive
Check drive dimensioning

PER

Program interference

A fault in the program sequence was detected Send controller with data (on diskette) to

Lenze

PR

Parameter reset

After switching on, a change in the software
version has been detected.
Automatic loading of factory setting.

Set the required parameters and save settings
under C003.

PR1 ... PR4 Parameter set error

Fault when reading a parameter set
CAUTION:
The factory setting is loaded automatically

Set the required parameters and save settings
under C003.

Sd1

Tacho fault

Short circuit or interruption of tacho cable

Check tacho cables for short-circuit or
interruption and remove fault

Sd2

Resolver fault

Resolver cable interrupted

Check resolver cable for open circuit
Check resolver
Acknowledge fault by mains switching

Sd3

Encoder fault at Dig_In 1 Incremental encoder or digital frequency cable

interrupted at X5
Input X5 PIN 8 not assigned

Check cable for open circuit
Assign input X5 PIN 8 with encoder potential
or switch off monitoring (C119 / C120)

Sd4

Encoder fault at Dig_In 2 Incremental encoder or digital frequency cable

interrupted at X9
Input X9 PIN 8 not assigned

Assign input X9 PIN 8 with encoder potential
or switch off monitoring (C119 / C120)

Sd5

Master current
interrupted

Interruption of the master current selection,
I

master

< 2mA

with master current selection 4...20mA, C034
= -1-

Remove interruption of the set-value cable or
select master selection 0...20 mA under C034
= -0-

SP

Wrong signal source
polarity

Tacho, resolver or fieldbus connection are
interchanged

Change tacho, resolver or fieldbus connection

U15

–15V supply interfered Overload / short-circuit terminal 20

Check load at terminal 20

–15 V supply defective

Return controller