Installation

4-31

48XX/49XXSHB0399

Signal cables

( Always screen digital and analog signal cables.

- Always connect the signal cables over the shortest possible distance with

the screen connections provided at the controller:

-

Connect both screen ends of digital signal cables.

( If potential differences are to be expected, lay an additional compensation

cable.

( For long signal cables, provide additional screening points:

- Connect the screen at the control cabinet input with a suitable clamp to

the conductive mounting plate of the control cabinet.

Remove the coating

Contact the screen
with a surface as large as possible

Screen braid

K35.0098

FIG 4-22

Additional screening connection on a mounting plate of the control cabinet

Filters

( Only use the mains filters and RFI filters which are designated for the

controller:

- RFI filters reduce impermissible high-frequency interference to a

permissible value.

- Mains chokes reduce low-frequency interference which depend on the

motor cable and its length.

Screening

Wire the screening and the GND and PE connections very carefully, to avoid
interference.

( All signal cables should be screened.
( Avoid a common terminal board for mains input and motor output.
( Route cable as close as possible to the reference potential. Free-hanging

cables have the same effect as aerials.