Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C610*

Input 1, addition
block 1

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C611*

Input 2, addition
block 1

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C612*

Input 3, addition
block 1

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C614*

Input 1, addition
block 2

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C615*

Input 2, addition
block 2

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C616*

Input 3, addition
block 2

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C620*

Gain dead band
element

1.00

-10.00

{0.01}

+ 10.00

C621*

Dead band,
dead band
element

1.0 %

0.0 %

{0.1 %}

100.0 %

C622*

Input, dead
band element

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

Display parameter only

C630*

Limiting
element 1
upper limit

100 % -100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

C630 must be higher than C631!

C631*

Limiting
element 1
lower limit

-100 % -100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

C631 must be lower than C630!

C632*

Input, limiting
element 1

0 %

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

Display parameter only

C635*

Limiting
element 2
upper limit

100 % -100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

C635 must be higher than C636!

C636*

Limiting
element 2
lower limit

-100 % -100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

C636 must be lower than C635!

C637*

Input, limiting
element 2

0 %

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

Display parameter only

C640*

PT1 element
Time constant

20ms

0.01 s

{0.01 s}

1 s

1 s

{0.1 s}

10 s

10 s

{1 s}

50 s