7-136

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C192*

¤ Input selection:

Fixed setpoint

1

-1-

Selection fixed setpoint 1

-2-

Selection fixed setpoint 2

...
-15-

Selection fixed setpoint 15

It is possible to set up to 15 setpoints with
freely selectable references:
1.Select fixed setpoint under C192.
2.Assign value under C193.
3.Enable via the digital inputs or C194.

C193*

Setpoint for
C192

-100.0 %

{0.1 %}

+ 100.0 %

100.0%

Fixed setpoint 1

75.0%

Fixed setpoint 2

50.0%

Fixed setpoint 3

25.0%

Fixed setpoint 4

0.0%

Fixed setpoint 5

...
0.0%

Fixed setpoint 15

C194*

¤ Enable fixed

setpoint

0

-0-

Free input is active

-1-

Fixed setpoint 1 is active

...
-15-

Fixed setpoint 15 is active

C195*

Delay
between
’engage brake’
and controller
inhibit

9999 s 0.00s

{0.01 s}

1s

1s

{0.1s}

10s

10s

{1s}

250s
9999 s

Delay between signal ’engage brake’ and
automatic controller inhibit
9999 s:
Unlimited delay, controller will not be
inhibited.

C196*

Delay between
’setpoint
integrator free’
and quick stop

0.00s

0.00 s

{0.01 s}

1 s

1s

{0.1s}

10s

10s

{1s}

100s

100s

{10s}

250s

Delay between reset of the quick stop
function and enable of the main setpoint
integrator

[C197*] Sign of the

torque selection

0

-0-

Sign is determined by the torque setpoint

-1-

positive sign

-2-

negative sign

Sign of the torque selection between reset
of QSP and enable of the setpoint
integrators

[C198*] Enable actual

speed filter

0

-0-

Filter not active

-1-

Filter active

C199*

Time constant
act. speed filter

10ms

8ms

{1ms}

100ms

C200*

Software
identification

String format: ”33S4902M_61000”

Display of the software version only via
interface.

C220*

Acceleration
time T

ir

of the

additional
setpoint

0.00 s 0.00 s

{0.01 s}

1 s

1 s

{0.1 s}

10 s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

C221*

Deceleration
time T

if

of the

additional
setpoint

0.00 s 0.00 s

{0.01 s}

1 s

1 s

{0.1 s}

10 s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

C222*

V

p

process

controller

1

0.1

{0.1}

10

10

{1.0}

500

Gain of the process controller

[C223*] T

n

process

controller

400 ms 20 ms

{1ms}

20000 ms
9999 ms

T

n

= 9999 ms: I-component switched-off

(only when controller is inhibited)

C224*

K

d

process

controller

0.0

0.0

¼ V

pn

{0.1

¼ V

pn

} 5.0

¼ V

pn

Differential component of the process
controller

[C230*] Control mode

for the override
field control

0

-0-

Limitation of the armature voltage

-1-

Control of the armature voltage

Field weakening must be permitted under
C231.