10 dead-band element, Configuration – Lenze EDS4900U-REG User Manual

Page 175

Advertising
background image

Configuration

7-84

48XX/49XXSHB0399

7.5.10

Dead-band element

Purpose

The dead-band element is used to set interferences around the zero point (e.g.
interference on analog input voltages) to digital zero.

Parameter setting

4900Str070

C 1 4 6 / C 1 4 7

C 1 4 5 / C 1 4 6

C 6 2 2

C 1 4 5 / C 1 4 6

± 2 0 0 %

C 6 2 0

C 6 2 1

I n p u t

O u t p u t 1

O u t p u t 2

FIG 7-43

Dead-band element

1. Input

With the function ”freely assignable analog inputs” each input can be assigned to
a ”terminal signal” from the table in C145.

2. Outputs

With the function ”freely assignable analog inputs” the outputs can be assigned to
the targets listed under C146.

The output signal is limited to max.

–200%.

3. Function

4900Str071

C 6 2 1

C 6 2 0

I n p u t

O u t p u t

FIG 7-44

Characteristic for the dead-band element

Code C621 determines the dead band. The gain is set under code C620. The
function is symmetrical to the zero position.

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

C620*

Gain dead
band
element

1.00

-10.00

{0.01}

+ 10.00

C621*

Dead band,
dead band
element

1.0 % 0.0 %

{0.1 %}

100.0 %

C622*

Input, dead
band
element

0%

-100.0 %

{0.1 %}

100.0 %

-200 %

{1 %}

+ 200 %

Display parameter only