Blocking protection for the motor, Configuration – Lenze EDS4900U-REG User Manual

Page 188

Advertising
background image

Configuration

7-97

48XX/49XXSHB0399

Message with pulse inhibit

In the event of a failure the ignition pulses are only inhibited for the armature circuit,
the digital output IMP is set, and one of the freely assignable digital output is set
(if the function ”Message” is assigned to the output). The message is automatically
indicated under C065 and it is entered in the history buffer. The history buffer is
deleted when switching off the mains.

Message without pulse inhibit

In the event of a failure one of the freely assignable digital outputs is set (if the
function ”Message” is assigned to the output). The message is automatically
indicated under C065 and it is entered in the history buffer. The history buffer is
deleted when switching off the mains.

Name

Lecom
No.

TRIP

Warning Message

with IMP

Message
without
IMP

can be
switched
off

OC5

I

¼t overload*

15

1

X

-

-

-

OC6

I

2

¼t overload*

16

X

X

-

-

1

OUE

Mains overvoltage*

22

1

X

-

-

-

LU1

Phase fault*

31

1

-

X

-

X

LU

Mains undervoltage

32

X

-

1

-

-

LF

Underfrequency*

41

1

-

X

-

-

OF

Overfrequency*

42

1

-

X

-

-

OH

Heat sink overtemperature*

50

1

X

-

-

-

CEO

Communication fault with option

61

1

X

-

-

X

U15

–15V supply interfered*

70

1

X

-

-

-

CCr

System fault

71

X

-

-

-

-

PR

Parameter fault

72

X

-

-

-

-

PR1

Parameter set 1 defective

72

X

-

-

-

-

PR2

Parameter set 2 defective

72

X

-

-

-

-

PR3

Parameter set 3 defective

72

X

-

-

-

-

PR4

Parameter set 4 defective

72

X

-

-

-

-

PER

Program error

73

X

-

-

-

-

SP

Wrong signal source polarity

80

1

X

-

-

X

Sd1

Analog encoder defective

81

1

X

-

-

X

Sd2

Resolver fault*

82

1

X

-

-

X

Sd3

Encoder fault at X5*

83

1

X

-

-

X

Sd4

Encoder fault at X9*

84

1

X

-

-

X

Sd5

Set-value encoder at 4mA...20mA
defective

85

1

X

-

-

X

EEr

External error*

91

1

X

X

X

-

dEr

Motor blocked

93

1

X

-

-

X

ACI

armature circuit interrupted

94

1

X

-

-

X

FCI

Field circuit interrupted

96

1

X

-

-

X

P03

Following error (tolerance exceeded) 153

X

X

X

1

X

P13

Angle overflow
(Detection not possible)

163

1

-

-

-

X

CE9

Communication monitoring
Serial interface

69

X

X

X

X

1

X = Selection possible

- = Selection not possible

1 = Default setting

*Achnowledgement not possible during TRIP