Configuration – Lenze EDS4900U-REG User Manual

Page 222

Advertising
background image

Configuration

7-131

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

[C117*] Function for

C116

-0-

No function

-1-

n

act

ˆ n

x

C017 (FDO1)

-2-

Controller enabled (FDO10)

-3-

n-controller output = M

max

(FDO2)

-4-

Ready for operation (RDY) (FDO11)

-5-

Pulse inhibit (IMP) (FDO12)

-6-

TRIP (relay)

-7-

Warning (FDO6)

-8-

Message (FDO7)

-9-

Ramp function generator on = off (FDO3)

-10-

n

act

= n

set

(FDO5)

-11-

n

act

= 0 (FDO4)

-12-

I

A

= 0 (FDO8)

-13-

I

A

& n

act

= 0 (FDO9)

-14-

'C046| or 'C049| >n

x

(threshold C243)

-15-

|I

A

| > I

x

(threshold C244)

-16-

I

F

> I

x

(threshold C245)

-17-

|n

act

| > n

x

(threshold C242)

-18-

Brake control

-19-

Comparator 1

-20-

Comparator 2

[C118]

Polarity for
C116

-0-

Output is HIGH active (FDO2, 3, 5)

-1-

Output is LOW active (FDO1, 4, relay)

C119*

¤ Selection of

monitoring
function

-15-

OC5

-16-

OC6

-22-

OUE

-31-

LU1

-32-

LU

-41-

LF

-42-

OF

-50-

OH

-61-

CE0

-70-

U15

-80-

SP

-81-

Sd1

-82-

Sd2

-83-

Sd3

-84-

Sd4

-85-

Sd5

-91-

EEr

-93-

dEr

-94-

ACI

-96-

FCI

-153-

P03

-163-

P13

-69-

CE9

I

¼t overload (controller protection)

I

2

¼t overload (motor protection)

Mains overvoltage
Phase fault
Mains undervoltage
Mains underfrequency f

mains

< 47Hz

Mains overfrequency f

mains

> 63Hz

Overtemperature heat sink
Communication error (automation
interface)
– 15V failure
Wrong signal source polarity
Tacho short-circuit/interruption
Open circuit of resolver
Encoder fault at X5
Encoder fault at X9
Defective setpoint encoder
Ext. TRIP terminal
Motor blocked
Interruption of armature circuit
Interruption of field circuit
Following error
Phase overflow
Communication error (serial interface)

[C120*] Change of

monitoring
function

-0-

TRIP

-1-

Warning

-2-

Message with pulse inhibit

-3-

Message without pulse inhibit

-4-

Switched-off

The important monitoring functions are set
according to the change of configuration
under C005.