Installation, Danger! (especially for hoist applications) – Lenze EDS4900U-REG User Manual

Page 58

Advertising
background image

Installation

4-20

48XX/49XXSHB0399

Relay output

Terminal

Use
(factory setting)

4900Str063

K11, K14

Floating relay output, contact load capacitiy: 50V / 0.5A (TRIP)

Additional digital inputs and outputs with 4X08...4X13

The controllers 4X08...4X13 are equipped with additional control terminals to
monitor the fuses. The following current flow charts show the factory setting of the
internal wiring and give suggestions on how to include an external fuse monitoring.

86

+ Vcc15

87

20

1

4908LP

4902MP

¥

External fuse monitoring

+ Vcc15

87
88
89

28

Ctrl. enable

2

4900Str013

¦

Without external fuse monitoring, terminal
20 can be directly connected with the
switch Ctrl. enable.

FIG 4-13

4808...4809 and 4908...4909

86

+ Vcc15

87

20

4911LP

4902MP

¥

Internal fuse monitoring

87
88
89

28

Ctrl. enable

1

4900Str_014

FIG 4-14

4811...4813 and 4911...4913

For monitoring, the terminals 86 and 89 should be connected in series with the
controller enable contact Ctrl. enable.

( For internal voltage supply (15 V), bridge the following terminals:

- X2/20 to 86

- X2/28 to 89

( For external voltage supply (24 V):

- Apply supply voltage to terminal 86.

- Bridge terminals 28 and 89.

Danger! (especially for hoist applications)

Please observe when connecting the fuse monitoring:
No torque is generated when the controller is inhibited.