Overload monitoring for the controller (I

¼t monitoring)

The I

¼t monitoring is designed for 150 % rated current.

4900Str083

P a r a m e t e r

P a r a m e t e r

T R I P

O v e r l o a d t i m e

R e c o v e r y t i m e

.

.

.

.

.

.

.

.

.
.

.

r

r

FIG 7-56

Overload diagram for 48XX/49XX controllers

The parameter I

1

/ I

rated

depends on the controller size. The ratio between

maximum current and rated armature current is indicated in chapter 3.3.

4900Str084

I

t

1

I

r a t e d

I 2

t 1

t 2

FIG 7-57

Possible current flow when using the full overload capacity of 48XX/49XX controllers

Examples for overload diagrams in FIG 7-56:

given

required

Result from diagram

Overload, I

1

= 1.3

ôI

rated

Overload time, t

1

= 70s

- I

2

= ? (basic load)

- t

2

= ? (recovery time)

I

2

= 0.6

ôI

rated

t

2

> 220 s

2. Basic load, I

2

= 0.8

ôI

rated

,

Recovery time t

2

 400s

- I

1

= ? (overload)

- t

1

= ? (overload time)

I

1

= 1.2

ôI

rated

t

1

$75s

For safety reasons, the ”I

¼t monitoring” is rated for continuous load with rated

armature current during mains switch-on.