Troubleshooting and fault elimination

8-8

48XX/49XXSHB0399

8.5.2

Checking the controller

Checking the power stage

Warning!

( The measurements described must only be carried out by specialists.
( Disconnect the controller from the mains.
( Tests should only be carried out when no voltage is applied!

Measurement

Measuring point

Measuring value

Semiconductor fuse

l

at the mains input

l

armature fuse

R

  0 W

R

  0 W

Internal fuses

R

  0 W

Thyristors

Disconnect armature cables:
A

“ B at the controller

B

“ A at the controller

R

“ Š

R

“ Š

Field controller

Disconnect field cables:
I+ , K-
I-, K+ (free-wheeling diode)

R

“ Š

R > 200k

W (diode   0.5V)

Checking the control board 4902MP

Checking the voltage supply:

( Wire up the controller completely
( Set controller inhibit (X2/28 open)
( Switch on the mains

Notes

Measuring point

Measured value

+ Vcc 15 V

X2/20

“ X3/40

+ 14.25 V...+ 15.75 V

+ Vref 10 V

X1/9

“ X3/40

+ 9.79 V...+ 10.21 V

-Vref 10 V

X1/10

“ X3/40

-9.79 V... -10.21 V