3 fault messages, Fault messages, Troubleshooting and fault elimination – Lenze EDS4900U-REG User Manual

Page 249

Advertising
background image

Troubleshooting and fault elimination

8-4

48XX/49XXSHB0399

8.3

Fault messages

Note!

If the fault message is interrogated by a fieldbus, the fault message is represented
not by an abbreviation but a LECOM no. read from C167.

Display

Cause

Remedy

---

No fault

-

-

ACI

Armature circuit
interrupted

Defective fuse in the armature circuit or cable
interruption

Check armature fuse or remove cable
interruption

CCr

System fault

Strong interference on control cables
Ground or earth loops in the wiring

Screen control cables
Check PE wiring (see chapter 4.4”Installation
of a CE-typical drive system”)

CE0

Communication fault
(automation interface)

Interference during transmission of control
commands via the automation interface

Check wiring

CE9

Communication fault
(serial interface)

Faulty messages from the serial interface.

Check wiring

dEr

Motor blocked

High standstill torque or motor mechanically
blocked.

Remove motor blockage or increase blocking
time under C124 or blocking current under
C123.

EEr

External fault (TRIP-Set)

A digital input assigned to the TRIP-Set
function has been activated

Check external encoder.
Check polarity to activate TRIP set under
C118.

FCI

Field circuit interrupted

Defective field fuses F1 and F2 or
interrupted field circuit.

Replace field fuses when no voltage is applied
or remove cable interruption.

LF

Mains underfrequency

Mains frequency < 47Hz

Check mains frequency,
controller must only be driven within a
frequency range from 47 to 63 Hz.

LU

Undervoltage

Mains voltage < 340 V or 410 V
(Variant 500 V mains voltage)
Mains synchronisation has not detected any
voltage zero for more than 25 ms.

Increase electronics supply separately with a
connected transformer or
use a controller with a lower mains connection
voltage.

LU1

Phase failure

Failure of the mains voltage or mains
interruption

Check mains voltage and remove mains
interruption
Adapt mains synchronisation to mains
conditions under C237.

OC5

Controller overload

Frequent or excessive acceleration with
overcurrent
Permanent overload with I

A

> 1.05 I

Arated

Check drive dimensioning

OC6

Motor is thermally
overloaded

Motor is thermally overloaded by, for instance,
- impermissibly high continuous currents
- frequent and excessive

acceleration processes

Check drive dimensioning

OF

Mains overfrequency

Mains frequency > 63Hz

Check mains frequency
Controller must only be driven within a
frequency range from 47 to 63 Hz.

OH

Heat sink temperature is
higher than the value set
in the controller

Ambient temperature
T

amb

> 45

•C or 35 •C

Heat sink very dirty
Incorrect mounting position

Allow controller to cool and ensure better
ventilation
Check ambient temperature in the control
cabinet
Clean heat sink
Change mounting position

Show/Hide Bookmarks