2 input of the motor data, Commissioning – Lenze EDS4900U-REG User Manual

Page 80

Advertising
background image

Commissioning

5-4

48XX/49XXSHB0399

5.2

Input of the motor data

Note

For internal calculations with field-weakening control, the exact input of the
following data is required. See indications on the nameplate of the connected
motor.

( C022, C023 Adapt maximum motor current I

max

( C081 Rated motor power for the power display
( C087 Rated motor speed for the power display
( C083 Rated field current for the field controller
( C084 L/R armature time constant for uncompensated motors
( C088 Rated motor current for ”I

2

¼t monitoring” (armature circuit)

( C090 Rated motor voltage for armature voltage limitation
Under C084 the controller can be adjusted to different armature time constants
T = L/R. The values can be set between 0 ms and 30 ms.

Common armature time constants: (see motor catalog, section I)

- compensated machines 0 ms to 10 ms

- uncompensated machines 15 ms to 30 ms.