Configuration – Lenze EDS4900U-REG User Manual

Page 223

Advertising
background image

Configuration

7-132

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C123

Current
threshold for
blocking
protection for
C124

0.95
I

rated

0 A

{0.1A}

100 A

100 A

{1 A}

3600 A

Rated current depends on the controller:
0 ... 87A

(4902)

0 ... 135A

(4903)

0 ... 270A

(4904)

0 ... 450A

(4905)

0 ... 720A

(4906)

0 ... 900A

(4907)

0 ... 1200A

(4X08)

0 ... 1800A

(4X09)

0 ... 2520A

(4X11)

0 ... 3600A

(4X12)

0 ... 4050A

(4X13)

See motor nameplate

C124*

Blocking time

60 s

1 s

{1 s}

100 s

Motor standstill time until TRIP is set

C125*

¤ Change of baud

rate for
interface

0

-0-

9600 baud

-1-

4800 baud

-2-

2400 baud

-3-

1200 baud

C126*

Delay
(Monitoring ser.
interface)

3000 s 0.2 s

{0.1 s}

10 s

10 s

{1 s}

100 s

100 s

{10 s}

3600 s

C128*

Delay for C116

0.000 s 0.000 s

{0.001 s}

240.000 s

Signal delay times for FDO 1...5 and relay
output.

C130*

Enable
additional T

i

times

0

-0-

T

ir

(C012) / T

if

(C013) active

-1-

T

ir1

/ T

if1

active

...
-15-

T

ir15

/ T

if15

active

If the T

i

times are enabled via terminal,

C130 is for display only.

C131*

¤ Ramp function

generator STOP

0

-0-

Enable ramp function generator

-1-

Stop ramp function generator

If ramp function generator STOP (main
setpoint) is enabled via terminal, C131 is
for display only.

C132*

¤ Ramp function

generator input
= 0

0

-0-

Enable mains setpoint at RFG input

-1-

Ramp function generator input = 0

[C134*] Ramp function

generator
characteristic

0

-0-

linear characteristic

-1-

S-shaped characteristic

C136*

FDI state

Bit

Free digital input

0

FDI 1

...
3

FDI 4

4

FDI 5

Only readable via LECOM. C136 indicates
the states of the digital inputs as a
decimal or binary value.The change of
polarity under C114 is considered in
C136.