Commissioning

5-6

48XX/49XXSHB0399

5.4

Selection of direction of rotation and quick stop

Direction of rotation

The polarity of the output voltage V

A

and thus the direction of rotation of the motor

depends on the signs of the setpoint, the control of the digital inputs X2/21 and
X2/22, and the polarity of the field voltage.

Quick stop (QSP)

Independently of the setpoint selection and because of the quick stop function, the
controller can be stopped within a time selectable under C105.

( The quick stop function is active:

- when the mains is switched on, if X2/21= HIGH and X2/22 = HIGH

- during operation with X2/21 = LOW and X2/22 = LOW

The speed is reduced to zero within the deceleration time set under C105.

( Quick stop

- sets the additional setpoint integrator to 0.

- decelerates the drive to 0 according to the deceleration ramp set under

C105.

- is detected internally if no signal has been applied to X2/21, X2/22 for

more than approx. 6 ms.

( The drive starts running again

- if a HIGH signal is applied to one of the inputs (also for keypad or interface

operation).

1

0

1

0

1

0

CCW

CW

QSP

2

1

4900Str027

FIG 5-3

Selection of direction of rotation

¥ CW/CCWnot overlapping
¦ CW/CCWoverlapping

When the threshold n

act

= 0 (C019) is reached, the integral action component of

the speed controller will be switched off (only if C005 = -10-, -11-, -40-, -41-). With
all other configurations, the I-component of the n-controller will only be switched
off, if the angle controller is not active (C254 = 0). The drive cannot generate a
torque when stopped by a brake.