Configuration

7-8

48XX/49XXSHB0399

Enable of additional acceleration and deceleration times

With terminal control, the inputs must be assigned according to the table below
to enable the additional acceleration and deceleration times. T

i

times can only be

activated in pairs.

input

2. input

3. input

4. input

T

ir1

, T

if1

1

0

0

0

T

ir2

, T

if2

0

1

0

0

T

ir3

, T

if3

1

1

0

0

T

ir4

, T

if4

0

0

1

0

T

ir5

, T

if5

1

0

1

0

T

ir6

, T

if6

0

1

1

0

T

ir7

, T

if7

1

1

1

0

T

ir8

, T

if8

0

0

0

1

T

ir9

, T

if9

1

0

0

1

T

ir10

,T

if10

0

1

0

1

T

ir11

,T

if11

1

1

0

1

T

ir12

,T

if12

0

0

1

1

T

ir13

,T

if13

1

0

1

1

T

ir14

,T

if14

0

1

1

1

T

ir15

,T

if15

1

1

1

1

The input with the lowest figure is the first input, the input with the next higher figure
is the second input, and so on (e. g. E4 = 1. input, E5 = 2. input).

C130 displays the momentarily active T

i

times.

With control via keypad or LECOM interfaces, C130 is used for the activation of
the T

i

times in pairs.

Code

Name

Possible settings

Lenze Selection

Info

C130*

¤ Enable of

additional
T

i

times

0

-0-

T

ir

(C012) / T

if

(C013) active

-1-

T

ir1

/ T

if1

active

...
-15-

T

ir15

/ T

if15

active

If the T

i

times are enabled via terminal,

C130 is for display only.

Show/Hide Bookmarks