Configuration

7-57

48XX/49XXSHB0399

7.4.2

Changeable parameter sets

Up to four different parameter sets can be created, for instance, to process
different materials with a machine or if different operating states (set-up operation,
stand-by, etc.) require different parameter sets.

Programming of parameter sets

Follow these steps to program several parmeter sets:

( Enter all setting required for your application.
( Select code C003 and store your parameter set

e. g. under -1- (parameter set 1).

( Enter all settings required for another application

(e. g. different material).

( Select code C003 and store this parameter set

e. g. under -2- (parameter set 2) etc.

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

C003

¤ Store

parameter
set

1

-1-

Parameter set 1

-2-

Parameter set 2

-3-

Parameter set 3

-4-

Parameter set 4

Note!

If the function “Load parameter set” is assigned to a digital input, the controller
evaluates the signal assigned to the input terminal.

Depending on the polarity, which is required for the activation of the input, selected
under C114, the assignment of the new function may start the loading of a
parameter set (RDY LED is off for approx. 1s).

Parameter changes carries out before and not stored under C003 are lost.

Parameter setting via keypad or LECOM interface:

1. For loading a parameter set under C114, select the polarity of the input

such that the input is deactivated during point 2..

2. Assign function “Load parameter set”

3. Store parameter set under C003

For parameter transfer to the drive via LECOM interface ensure, that the parameter
which selects the input polarity (C114)is set before the function assignment (C113)
is transmitted.