Configuration – Lenze EDS4900U-REG User Manual

Page 203

Advertising
background image

Configuration

7-112

48XX/49XXSHB0399

Acceptance with SH + PRG

The controller accepts the changed parameter only after pressing SH+PRG.

1. Select a code using

s or t.

2. Change to the parameter level using PRG.

3. Change a parameter (even while the drive is running) using

s or t.

4. Press SH + PRG. ( --ok-- is displayed for approx. 0.5 s)

The controller now works with the new parameter.

Code level

Parameter level

C

8 3

0 . 0

A

Code

Parameter

Unit

0

0

F I E L D

C U R R E N T

PRG

C

8 3

0 . 0

F I E L D

C U R R E N T

A

0

0

Code

Parameter

Unit

Change a parameter
with

s or t

C

8 3

.

A

0

0

1

2

F I E L D

C U R R E N T

Code

Parameter

Unit

SH + PRG

C

8 3

.

A

0

0

1

2

F I E L D

C U R R E N T

Code

Parameter

Unit

Acceptance with SH + PRG when the controller is inhibited

The controller only accepts the changed parameter when the controller is inhibited
and after pressing SH + PRG.

1. Select a code using

s or t

2. Change to the parameter level using PRG.

3. Change a parameter (even if the drive is running) using

s or t .

4. Press STP to inhibit the controller.

5. Press SH + PRG. ( --ok-- is displayed for approx. 0.5 s)

6. Press SH + STP to enable the controller again

The controller now works with the new parameter.

Code level

Parameter level

C

t

r

o

0 0 5

- 1 1 -

C

n f i g u

a

i o n

Code

Parameter

Unit

PRG

C 0 0 5

- 1

-

S P E E D

C T R L

T A C H O

1

Code

Parameter

Unit

Change a parameter

with

s or t

C

.

t

r

o

0 0 5

- 1

-

C

n f i g u

a

i o n

0

Code

Parameter

Unit

STP

2. SH + PRG

C 0 0 5

- 1

-

0

Code

Parameter

Unit

S P E E D

C T R L

A R M A T

Show/Hide Bookmarks

Advertising