Configuration

7-140

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C320*

V

p2

of the n-

controller
adaption

8

1

{1}

1000

Second gain factor for speed controller
adaption

C321*

V

p3

of the n-

controller
adaption

8

1

{1}

1000

Third gain factor for speed controller
adaption

C322*

n

1

of the n-

controller
adaption

3000

rpm

0 rpm

{1 rpm}

5000 rpm

Speed setpoint threshold of speed
controller adaption, condition: n

1

> n

0

C323*

n

0

of the n-

controller
adaption

50 rpm 0 rpm

{1 rpm}

5000 rpm

Speed setpoint threshold of speed
controller adaption, condition: n

1

> n

0

C324*

¤ n-controller

adaption on/off

0

-0-

n-controller adaption is off

-1-

n-controller adaption is on

C325*

V

p2

of the

process
controller
adaption

1

0.1

{0.1}

10

10

{1}

500

Second gain factor for process controller
adaption

C326*

V

p3

of the

process
controller
adaption

1

0.1

{0.1}

10

10

{1}

500

Third gain factor for process controller
adaption

C327*

set2 of the
process
controller
adaption

100 % 0.0 %

{0.1 %}

100.0 %

Setpoint speed threshold of the process
controller adaption, condition: set2 > set1

C328*

set1 of the
process
controller
adaption

0%

0.0 %

{0.1 %}

100.0 %

Setpoint speed threshold of the process
controller adaption, condition: set2 > set1

C329*

¤ Process

controller
adaption on/off

0

-0-

Process controller adaption is off

-1-

Process controller adaption is on

C330*

Setpoint of the
process
controller

0%

-100.0 %

{0.1 %}

100.0 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C331*

Evaluation of
the process ctrl.
output

100 % -100.0 %

{0.1%}

100.0 %

If an analog signal source (C145/C146) is
assigned, the parameter will be displayed
only.

C332*

Acceleration
time T

ir

of the

process
controller
setpoint

0.00 s 0.00 s

{0.01 s}

1.00 s

1.0 s

{0.1 s}

10.0 s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

C333*

Deceleration
time T

if

of the

process ctrl.
setpoint

0.00 s 0.00 s

{0.01 s}

1.00 s

1.0 s

{0.1 s}

10.0 s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

C334*

Acceleration
time T

ir

of the

process ctrl.
evaluation

0.00 s 0.00 s

{0.01 s}

1.00 s

1.0 s

{0.1 s}

10.0 s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

C335*

Deceleration
time T

if

of the

process ctrl.
evaluation

0.00 s 0.00 s

{0.01 s}

1.00 s

1.0 s

{0.1 s}

10.0 s

10 s

{1 s}

100 s

100 s

{10 s}

990 s