Configuration – Lenze EDS4900U-REG User Manual

Page 114

Advertising
background image

Configuration

7-23

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

[C115*] Priority for

C112

-0-

Deactivate terminal function, if terminal control
is switched-off under C001. (X2/E4, E5)

-1-

Terminal function remains active, if terminal
control is switched-off under C001. (X2/E1, E2,
E3)

C136*

FDI
Status

Bit

Free digital input

0

FDI 1

...
3

FDI 4

4

FDI 5

Only readable via LECOM.
C136 indicates the states of the digital
inputs as decimal or binary value. The
change of polarity under C114 is
considered in C136.

Example for enable of additional T

i

time for terminal E2

( C112 -2- Digital input X2/E2
( C113 -1- Enable additional T

i

times

C 1 1 2

E 1
E 2
E 3

E 5

C 1 1 5

C 1 1 4

C 1 1 3

C 0 0 1

O p e r a t i n g m o d e

P r i o r i t y

L e v e l

T e r m i n a l s e l e c t i o n

S i g n a l s e l e c t i o n

N o s i g n a l

A d d i t i o n a l T i - t i m e s
J O G s e t p o i n t s

R F G z e r o

4900Str035

FIG 7-8

Parameter assignment for digital inputs

Except the functions ”Enable JOG set-values”, ”Enable additional acceleration and
deceleration times”, ”Enable fixed set-values” and ”Select parameter set”, each
function can only be assigned to one terminal. An already assigned function will be
overwritting by re-assigning the input.

A function, which is already assigned to an input, can only be assigned to another
terminal, if the input used before is assigned with a new function.

LECOM code for FDI

The states of FDI (E1 ... E5) can be displayed in binar format in C136 or they can
be read out in HEX format via the LECOM interface.

FDI assignment in C136:

Bit 15

.........

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

not assigned

FDI5

FDI4

FDI3

FDI2

FDI1