Possible settings

Name

Code

Info

Selection

Lenze

Name

C026

¤ Encoder

constant for
C025

0mV

C025 = -1-, -2-, -3-, -4-:
Offset correction of the analog inputs
-9999mV

{1mV}

+ 9999mV

The encoder constants are not overwritten
the factory setting is loaded.

0V

C025 = -5-:
Offset correction of the armature voltage feedback
-100V

{1V}

+ 100V

1

C025 = -10-, -11-:
Encoder constant of the digital frequency inputs
-0-

8192 increments / revolution

-1-

4096 increments / revolution

-2-

2048 increments / revolution

-3-

1024 increments / revolution

-4-

512 increments / revolution

-5-

256 increments / revolution

3

C025 = -13-:

Encoder constant of the encoder outputs with resolver
feedback

-1-

256 increments / revolution

-2-

512 increments / revolution

-3-

1024 increments / revolution

-4-

2048 increments / revolution

C027

Gain factor for
C025

1.000 C025 = -1-, -2-, -3-, -4-:

Gain factor of the analog inputs

-2.500

{0.001}

+ 2.500

1.000 C005 = -11-, -41-:

Gain factor of the tacho input X1/3, X1/4

0.010

{0.001}

+ 9.999

1.010 C025 = -5-:

Gain factor of the armature voltage feedback

0.100

{0.001}

+ 9.999

0.1000 C025 = -10-, -11-:

Gain factor of the digital frequency inputs

-3.2767 {0.0001}

+ 3.2767

If an analog signal source (C145/C146) is
assigned, only the parameter will be
displayed.

1.000 C025 = -12-:

Gain factor of the resolvers

-32.767 {0.001}

+ 32.767

C028

Divisor for C025 0.1000 C025 = -10-, -11-:

Divisor for the digital frequency inputs
0.0001

{0.0001}

3.2767

C029

¤ Automatic

adjustment for
C025

Applies to all configurations:
If an automatic adjustment is not possible,
the previous value will be maintained.
--ok-- will not be displayed.

C025 = -1-, -2-, -3-, -4-:
Automatic adjustment for analog inputs
-100%

{0.1%}

100.0%

1.Inhibit controller.
2.Set the setpoint at the terminal selected
3.Enter the corresponding value.
4.C027 displays the calculated gain factor

C025 = -2- and tacho at X1/3, X1/4 or
C025 = -5- and actual value from armature voltage

feedback:

n

act

adjustment

0 rpm

{1rpm}

5000rpm

Adjustment during operation:
1.Display of actual speed.
2.Measure real speed with hand tacho.
3.Enter real speed.
4.Drive accelerates to this speed.
5.C027 displays the calculated gain

factor.