Configuration – Lenze EDS4900U-REG User Manual

Page 219

Advertising
background image

Configuration

7-128

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C088

Rated motor
current

0 A

{0.1A}

100 A

100 A

{1A}

3600 A

Rated current depends on the controller:
0..87A

(4902)

0..135A (4903)
0..270A (4904)
0..450A (4905)
0..720A (4906)
0..900A (4907)
0..1200A (4X08)
0..1800A (4X09)
0..2520A (4X11)
0..3600A (4X12)
0..4050A (4X13)
See motor nameplate

C090

¤ Rated motor

voltage

420 V

150 V

{1 V}

650 V

See motor nameplate
Observe max. permissible output voltage
of the controller!

C093*

¤ Controller

identification

49XX

Display: controller type

C094*

User password

0

0

{1}

999

0 = No password protection (see also
C000)

C098

Language

0

-0-

German

-1-

English

-2-

French

C099*

Software
version

49 6.X

Display: Series and software version

C100*

¤ Input selection:

Additional
acceleration and
deceleration
times for main
setpoint

-1-

Acceleration time T

ir1

/deceleration time T

if1

-2-

Acceleration time T

ir2

/deceleration time T

if2

...
-15-

Acceleration time T

ir15

/deceleration time T

if15

Extends T

ir

(C012) and T

if

(C013) by max.

15 value pairs. Can be changed under
C130:
1.Select additional times under C100.
2.Set under C101 (T

ir

) or C103 (T

if

).

C101*

Acceleration
time for C100

0.00s

0 s

{0.01 s}

1 s

1 s

{0.1s}

10s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

Time refers to speed change 0...n

max

C103*

Deceleration
time for C100

0.00s

0 s

{0.01 s}

1 s

1 s

{0.1s}

10s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

Time refers to speed change 0...n

max

C105

Deceleration
time for quick
stop

0.00s

0 s

{0.01 s}

1 s

1 s

{0.1s}

10s

10 s

{1 s}

100 s

100 s

{10 s}

990 s

Time refers to speed change 0...n

max

C108*

Gain for C110

1.00

-10.000 {0.001}

+ 10.000

Gain for X4/62, X4/63, X8

C109*

Offset for C110

0mV

-10000mV

{1mV}

+ 10000mV

Offset for X4/62, X4/63
Loading of the factory settings does not
overwrite C109.
This code is only effective if the digital
frequency output is selected under C110.

C110*

¤ Input selection:

Monitor output

1

-1-

Analog output X4/62 (monitor 1)

-2-

Analog output X4/63 (monitor 2)

-3-

Digital frequency output X8

The monitor outputs are freely assignable
with the signals under C111:
1.Select monitor output under C110.
2.Assign signals under C111.
3.If necessary, adjust under C108 and

C109.