Configuration – Lenze EDS4900U-REG User Manual
Page 217
![background image](/manuals/566281/217/background.png)
Configuration
7-126
48XX/49XXSHB0399
Code
Possible settings
Name
Code
Info
Selection
Lenze
Name
C067
Fault indication:
TRIP
Display
Meaning
---
no fault at present
ACI
armature circuit break
CCr
System fault
CE0
communication error (automation interface)
CE9
communication error (serial interface)
dEr
motor blocked or field break
EEr
external TRIP (from terminal)
FCI
break excitation circuit
LF
mains frequency fault f
mains
< 47Hz
LU
Undervoltage
LU1
fa lty phase mains break
When a TRIP occurs:
1.The display changes to C067.
2.TRIP blinks until the fault and the
memory are reset.
Reset memory:
with SH+ PRG or via the input
TRIP-Reset, with LECOM via C043 or via
the input TRIP-Reset
3.TRIP is entered into the history buffer of
C067.
The last 8 entries can be displayed by
pressing ▼ and ▲. The TRIP saved last
is displa ed first The histor b ffer isn’t
LU1
faulty phase, mains break
OC5
I
¼t overload (controller protection)
OC6
I
2
¼t overload (motor protection)
OF
mains frequency fault f
mains
> 63Hz
OH
overtemperature heat sink
OUE
mains overvoltage
P03
following error (tolerance exceeded)
P13
angle overrun
(angle difference cannot be compensated any
longer)
PER
software error
(please contact Lenze)
PR
all parameters reset (factory setting)
is displayed first. The history buffer isn’t
cleared when the mains switched on.
After PR-TRIP, the code C180 must be
reset to 2Q operation for controllers 48XX
or for 2Q applications.
PR
all parameters reset (factory setting)
PR1
parameter set 1 reset (factory setting)
PR2
parameter set 2 reset (factory setting)
PR3
parameter set 3 reset (factory setting)
PR4
parameter set 4 reset (factory setting)
Sd1
short circuit or interruption of tacho
Sd2
open circuit of resolver
Sd3
encoder fault at X5
Sd4
encoder fault at X9
Sd5
master current < 2 mA with C034 = -1-
SP
wrong signal source polarity
U15
15V supply voltage is missing
C068
Operating state
Bit
Meaning
0-3
Operation error (bit-decoded)
4-7
Communication error (bit-coded)
8
Controller enable
9
n
act
= 0
10
Setpoint inversion
11
Pulse inhibit
12
Quick stop
13
I
max
limit reached
14
n
act
= n
set
15
TRIP fault message
16 bit status information
Only readable via LECOM. The signals are
described in the Lecom-A/B protocol.