Configuration

7-126

48XX/49XXSHB0399

Code

Possible settings

Name

Code

Info

Selection

Lenze

Name

C067

Fault indication:
TRIP

Display

Meaning

---

no fault at present

ACI

armature circuit break

CCr

System fault

CE0

communication error (automation interface)

CE9

communication error (serial interface)

dEr

motor blocked or field break

EEr

external TRIP (from terminal)

FCI

break excitation circuit

LF

mains frequency fault f

mains

< 47Hz

LU

Undervoltage

LU1

fa lty phase mains break

When a TRIP occurs:
1.The display changes to C067.
2.TRIP blinks until the fault and the

memory are reset.
Reset memory:
with SH+ PRG or via the input
TRIP-Reset, with LECOM via C043 or via
the input TRIP-Reset

3.TRIP is entered into the history buffer of

C067.
The last 8 entries can be displayed by
pressing ▼ and ▲. The TRIP saved last
is displa ed first The histor b ffer isn’t

LU1

faulty phase, mains break

OC5

I

¼t overload (controller protection)

OC6

I

2

¼t overload (motor protection)

OF

mains frequency fault f

mains

> 63Hz

OH

overtemperature heat sink

OUE

mains overvoltage

P03

following error (tolerance exceeded)

P13

angle overrun
(angle difference cannot be compensated any
longer)

PER

software error
(please contact Lenze)

PR

all parameters reset (factory setting)

is displayed first. The history buffer isn’t
cleared when the mains switched on.

After PR-TRIP, the code C180 must be
reset to 2Q operation for controllers 48XX
or for 2Q applications.

PR

all parameters reset (factory setting)

PR1

parameter set 1 reset (factory setting)

PR2

parameter set 2 reset (factory setting)

PR3

parameter set 3 reset (factory setting)

PR4

parameter set 4 reset (factory setting)

Sd1

short circuit or interruption of tacho

Sd2

open circuit of resolver

Sd3

encoder fault at X5

Sd4

encoder fault at X9

Sd5

master current < 2 mA with C034 = -1-

SP

wrong signal source polarity

U15

–15V supply voltage is missing

C068

Operating state

Bit

Meaning

0-3

Operation error (bit-decoded)

4-7

Communication error (bit-coded)

8

Controller enable

9

n

act

= 0

10

Setpoint inversion

11

Pulse inhibit

12

Quick stop

13

I

max

limit reached

14

n

act

= n

set

15

TRIP fault message

16 bit status information
Only readable via LECOM. The signals are
described in the Lecom-A/B protocol.