Configuration

7-59

48XX/49XXSHB0399

When the function ”load parameter set” is activated, the controller cannot react on
any other signal for approx. 1 second. Therefore, the ”Ready message” (RDY) at
terminal 44 will not be displayed for the time the controller cannot react on control
signals (e.g. controller enable).

For control and parameter setting via the keypad or LECOM interfaces, a
parameter set can be loaded via C002. Here, also default setting is available.

Code

Name

Possible settings

Code

Name

Lenze Selection

Info

[C002]

Load
parameter
set

0

-0-

Factory setting

-1-

Parameter set 1

-2-

Parameter set 2

-3-

Parameter set 3

-4-

Parameter set 4

Parameter set 1 is automatically loaded
after mains connection. If another
parameter set is selected via terminal, the
selected parameter set will be loaded
additionally.

Default setting: Parameter set 2 for dancer position control

As application support, a parameter set for dancer position control at an unwinder
with diameter precontrol is stored in parameter set 2 in default setting. This
parameter set is meant as example for the adaptation to your application.

Changes compared with parameter set 1, default setting

Code

Parameter

Meaning

C000

-2-

Expanded code set

C005

-11-

Speed control with tacho feedback

C145

-4-

Select terminal 8

C146

-15-

Assign arithmetic block input 1 to terminal 8

C145

-3-

Select terminal 6

C146

-16-

Assign arithmetic block input 2 to terminal 6

C145

-10-

Select arithmetic block 2 output

C146

-1-

Assign arithmetic block 2 output main set-value to C046

C145

-9-

Select process controller output

C146

-3-

Assign additional set-value C049 to process controller output

C145

-1-

Select terminal 1,2

C146

-7-

Assign actual process controller value to terminal 1,2

C112

-3-

Select digital terminal E3

C113

-32-

Assign E3 to the process controller suppression

C112

-5-

Select digital terminal E5

C113

-31-

Assign E5 to suppress the I component of the process
controller

C191

-4-

Arithmetic block 2: input1 / input2

Proceed as follows to activate this parameter set:

( C002 = -2-, load parameter set 2
( C003 = -1-, store under parameter set 1
After the adaptation and optimisation of the parameters, store the parameter set
with C003.