( Ensure free installation space above and below the controller:

- 100 mm for 4902...4907

- 150 mm for 4X08...4X13

( Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
( If the cooling air contains pollutants (dust, fluff, grease, aggressive gases),

which may impair the function of the controller:

- Take suitable preventive measures , e.g. separate air duct, installation of

filters, regular cleaning, etc.

( Do not exeed the ambient temperature permissible during operation:

- 4902...4906: to 45

°C: without power derating

- 4907, 4X08...4X13: to 35

°C: without power derating

35

°C to max. 45 °C: power derating 1% / K

Possible mounting positions

( Only vertical controller installation:

- 4902 ... 4907, 4X08 and 4X09 with mains connections on top

- 4X11 ... 4X13 with mains connections at bottom